About MGM Services Education Center Medical Gas Matters Newsletter Products Related Support Feedback Employment
MGM ServicesEducation CenterMedical Gas Matters! NewsletterRelated Support LinksFeedbackEmploymentAbout MGM

Volume 2, Issue 2

© 2001 Medical Gas Management, LLC
Main Index

IN THIS ISSUE

Pipe Dreams – Hyperbaric Supply Systems
Particulate Matters
MGM to Host ISO Meeting
What? How? When? Why?
Installer's School Schedule 2001
Beyond the Walls…


PIPE DREAMS – Hyperbaric Supply Systems

Fred Evans, CEO
Medical Gas Management, LLC

Hyperbaric medicine in healthcare facilities is on the rise. Hyperbaric chambers and related equipment purchases bring additional challenges to facility managers in dealing with the supply of higher than normal pressures of oxygen and medical air.

Hyperbaric chamber technicians prefer the main line pressure to be 70 PSIG. Since the main oxygen supply line is set between 50–55 PSIG, we are left with the challenge of finding oxygen at higher pressure. There are basically two ways to supply both the volume and pressure requested.

Chapter 19 of NFPA 99, 1999 deals with hyperbaric chambers, and refers to the source of supply and piping distribution in Chapter 4.

Option 1: Connect a new oxygen supply line after the oxygen primary regulator. Equip it with a duplexed high-pressure main line regulator assembly, source valve, main shut off valve, high-pressure inlet, and a high/low pressure switch connected to the master alarm panels. You will also need to provide a zone valve outside the treatment area.

If the clinical staff requires access to the normal line pressure for ventilators or low flow therapy, you may also be required to pipe the room just like other patient care areas.

Option 2: Provide new, smaller bulk and reserve supply of oxygen dedicated to the hyperbaric treatment facility. The system is designed like the normal supply line.

Caution – when calculating the size of the main line, remember each chambers use could be as much as 21 SCFM. Line size should be between 1” and 2” depending on the distance.

Medical Air is also applicable for hyperbaric “air break” treatments. The normal equipment needs are a high pressure medical manifold with at least 2 “H” size cylinders on each bank. Each cylinder contains 250 cubic feet of gas, so this provides a total of 1000 cubic feet. If the medical air is piped, it also is required to meet NFPA 99, 1999 and shall include source valve, main valve, high-low pressure switch, zone valve and area alarm.

For more information on hyperbaric supply systems, call 1-800-732-9035.

BACK
TO TOP


Particulate Matters

Skip Langley

Particulate matter – the dirt and debris trapped in medical gas piping and outlets. It reduces efficiency and causes excess wear on parts and equipment and can compromise patient safety. As medical gas professionals, how are we to deal with this problem?

The NFPA 99, Standard for Health Care Facilities 1999 edition, addresses this issue in section 4-3.4.1.2 (a)... Blow Down After installation of piping, but before installation of station outlets and other medical gas system components (e.g., pressure-actuating switches for alarms, manifolds, pressure gauges, or pressure relief valves), the line shall be blown clear by means of oil-free, dry nitrogen...”

The Standard says in section 4-3.4.1.2.(d)...Piping Purge Test, “In order to remove particulate matter in the pipelines, a heavy, intermittent purging of the pipeline shall be done. The appropriate adapter shall be obtained, and a high-flow purge shall be put on each outlet. The outlet shall be allowed to flow fully until the purge produces no discoloration in a white cloth.” (Commonly called the white cloth test.)

Because these requirements appear in the Installer Performance Testing section of the Standard, the assumption is almost always that the blow down and pipe purge test are to be done after all installation is completed. BUT, that is clearly not the intent nor wording of the Standard!

If the Blow Down in 4-3.4.1.2.(a) is not done before connecting the outlets and other components, then all construction debris is forced into those components and trapped behind the outlet secondary check valves during the Piping Purge Test of 4-3.4.1.2.(d).

This is usually the heaviest of the construction particulate, and most will not pass through the check valve during the purge. This heavy particulate remains in the outlet, causing o-ring damage and leaks, and being broken down by turbulence and eventually coming out of the outlet to compromise the patient care equipment or even the patient’s airway.

It is imperative that all installers comply with the letter of the code in this matter; and that the certifier, at the very least, does random inspection behind secondary check valves, and in pressure switches and gauges, to verify that this problem does not exist.

It is a sign of a careful installer when he or she purges, both during brazing and during blow downs, away from the outlets and components...from the smallest to the largest piping.

It should also be noted that volume moves particulate, not just pressure. Pressure is a tool for increasing volume, but diameter and time are also factors. Volume and velocity are what moves particulate matter. Let’s all work to move them AWAY from the patient and the patient equipment system components.

BACK
TO TOP


MGM to Host ISO Meeting

Delegates to the International Standards of Operations, TC 121, SC 6 have selected the Corporate Office of Medical Gas Management, LLC as the site for their meeting in February 2001.

Delegates from: Australia, Canada, Great Britain, Germany, Italy, Japan, New Zealand Sweden and the US will be hosted by Fred Evans for 5 days of discussions. A variety of topics related to anesthetic and respiratory equipment, medical gas systems design and safety issues are on the agenda.

“It is an honor to have this distinguished delegation visit the MGM offices and Oklahoma City,” says Evans. “I look forward to the challenges presented in the development of international standards and am confident we will accomplish good work in our meetings.”
BACK
TO TOP


What? How? When? Why?

Need an answer to a question about your medical gas system? Whether it is code compliance, a design issue, equipment specification, preventative maintenance or repairs, we can help. Our experts will answer your questions in the Facilities Forum column of an upcoming issue of Medical Gas Matters!

Write us at:
Medical Gas Management, LLC
Facilities Forum
5600 Philip J. Rhoads Avenue
Bethany, OK 73008

Or e-mail your questions to: feedback@mgmusa.com

All submissions become the property of Medical Gas Management, LLC

BACK
TO TOP


Installer's School Schedule 2001

March 28, 29 & 30
May 16, 17 & 18
July 25, 26 & 27
September 19, 20 & 21
November 14, 15 & 16

MGM will offer Medical Gas Installer’s School classes at our Education Center in Bethany, OK on the dates listed above. Make plans to attend one of the sessions to become a certified medical gas installer. To register on line, visit our web site: www.mgmusa.com, or call Jan at (800) 732-9035.

MGM's Teaching Exhibit demonstrates how a medical gas system should look "Beyond the Walls".





1. Pressure Gauges and Switches
2. Headwall and Outlets
3. Area Alarm Panel
4. Manifold

BACK
TO TOP


Beyond The Walls…

Proper maintenance could have saved this facility a great deal of replacement expense.

MGM was called to service this medical air compressor and dryer. The liquid ring pumps leaked so badly that a cardboard shield was installed to prevent the “sprinkler effect” of leaks from drenching and shorting out other equipment in the room.

Mixed piping materials, corrosive action of water and minerals, flux and soft solder contributed large amounts of contamination to medical air and surgical dental air supplied by this source. Copper medical air main lines downstream of this unit were damaged beyond repair and had to be replaced.

BACK
TO TOP